Toa Denki.Co.Ltd
電線 許容電流早見表
VVケーブル
サイズ |
@
IV電線
周囲温度
30度以下 |
A VVケーブル(周囲温度30度以下)
同一管、線又はダクト内に収める電線数 |
BVVケーブル
(周囲温度40度)
気中及び暗渠布設 |
3
以下 |
4 |
5〜6 |
7〜15 |
16〜40 |
41〜60 |
61
以上 |
単心
3条 |
2心
1条 |
3心
1条 |
1.2 |
(19) |
(13) |
(12) |
(10) |
(9) |
(8) |
(7) |
(6) |
|
|
|
1.6 |
27 |
19 |
17 |
15 |
13 |
12 |
11 |
9 |
|
|
|
2.0 |
35 |
24 |
22 |
19 |
17 |
15 |
14 |
12 |
|
|
|
2.6 |
48 |
33 |
30 |
27 |
23 |
21 |
19 |
17 |
|
|
|
3.2 |
62 |
43 |
38 |
34 |
30 |
27 |
24 |
21 |
|
|
|
2 |
27 |
|
|
|
|
|
|
|
20 |
18 |
15 |
3.5 |
37 |
|
|
|
|
|
|
|
28 |
25 |
21 |
5.5 |
49 |
34 |
31 |
27 |
24 |
21 |
19 |
16 |
37 |
33 |
28 |
8 |
61 |
42 |
38 |
34 |
30 |
26 |
24 |
21 |
47 |
42 |
36 |
14 |
88 |
61 |
55 |
49 |
43 |
38 |
34 |
30 |
66 |
59 |
50 |
22 |
115 |
80 |
72 |
64 |
56 |
49 |
45 |
39 |
88 |
78 |
66 |
38 |
162 |
113 |
102 |
90 |
79 |
70 |
63 |
55 |
120 |
110 |
93 |
60 |
217 |
152 |
136 |
121 |
106 |
93 |
85 |
74 |
165 |
145 |
120 |
100 |
298 |
208 |
187 |
167 |
146 |
128 |
116 |
101 |
230 |
200 |
165 |
150 |
395 |
276 |
249 |
221 |
193 |
170 |
154 |
134 |
295 |
255 |
220 |
200 |
469 |
328 |
395 |
262 |
230 |
202 |
183 |
159 |
350 |
310 |
260 |
250 |
556 |
389 |
350 |
311 |
272 |
239 |
217 |
189 |
400 |
0355 |
300 |
325 |
650 |
455 |
409 |
364 |
318 |
280 |
254 |
221 |
470 |
420 |
355 |
400 |
556 |
521 |
469 |
417 |
365 |
320 |
291 |
253 |
525 |
|
|
500 |
842 |
589 |
530 |
471 |
412 |
362 |
328 |
286 |
590 |
|
|
(注) −条件ー
@ IV電線:碍子引き配線により、絶縁物の最高許容温度60℃で施設する場合
A VVケーブル:電線管などに絶縁物の最高許容温度60℃のIV電線、
及び、VVケーブルなどを収める場合。
B VVケーブル:気中、及び、暗渠布設に置けるもの。
尚、銅電線1.6mm、及び、断面積2mm2未満の物は、一般的には配線に使用する電線
として認められていない。 従って、( )内の数値は参考として示したものです。
許容電流早見表
3心(共通シース形)
600V及び、3300V〜6600V CVケーブル
布設条件 |
気中布設 |
直 埋 布 設( 深さ1,400mm) |
|
1条
(1回線) |
1条
(1回線) |
2条
(2回線) |
31条
(3回線) |
|
直射日光
(日射) |
損失率
( LF ) |
損失率
( LF ) |
損失率
( LF ) |
|
無 |
有 |
0.6 |
0.8 |
1.0 |
0.6 |
0.8 |
1.0 |
0.6 |
0.8 |
1.0 |
600V 325 |
555 |
475 |
640 |
580 |
535 |
555 |
500 |
455 |
490 |
435 |
395 |
250 |
470 |
410 |
560 |
505 |
470 |
485 |
435 |
395 |
425 |
380 |
345 |
200 |
410 |
360 |
495 |
450 |
415 |
430 |
385 |
355 |
380 |
335 |
305 |
150 |
340 |
310 |
430 |
390 |
360 |
370 |
330 |
305 |
325 |
290 |
260 |
100 |
260 |
245 |
345 |
310 |
290 |
295 |
265 |
245 |
260 |
230 |
210 |
60 |
190 |
180 |
260 |
235 |
220 |
225 |
200 |
185 |
195 |
175 |
160 |
38 |
140 |
135 |
205 |
185 |
170 |
175 |
155 |
140 |
150 |
135 |
120 |
22 |
100 |
100 |
145 |
135 |
125 |
125 |
115 |
105 |
110 |
100 |
92 |
14 |
77 |
76 |
115 |
105 |
98 |
100 |
90 |
83 |
88 |
78 |
71 |
8 |
65 |
55 |
84 |
77 |
72 |
73 |
66 |
61 |
64 |
58 |
53 |
5.5 |
44 |
45 |
68 |
63 |
59 |
59 |
54 |
50 |
53 |
47 |
43 |
3.5 |
33 |
34 |
53 |
49 |
46 |
46 |
42 |
39 |
41 |
37 |
34 |
2 |
24 |
25 |
38 |
35 |
33 |
34 |
31 |
28 |
30 |
27 |
25 |
3K-6K325 |
555 |
455 |
615 |
565 |
525 |
545 |
490 |
455 |
485 |
435 |
395 |
250 |
470 |
390 |
535 |
490 |
455 |
470 |
430 |
395 |
420 |
375 |
345 |
200 |
410 |
345 |
475 |
435 |
405 |
420 |
380 |
350 |
375 |
335 |
305 |
150 |
345 |
295 |
405 |
375 |
350 |
360 |
325 |
300 |
320 |
285 |
260 |
100 |
265 |
235 |
325 |
300 |
280 |
285 |
260 |
240 |
255 |
230 |
210 |
60 |
190 |
175 |
240 |
225 |
210 |
215 |
195 |
180 |
190 |
170 |
160 |
38 |
145 |
130 |
185 |
175 |
160 |
165 |
150 |
140 |
150 |
135 |
120 |
22 |
105 |
98 |
135 |
125 |
120 |
120 |
110 |
105 |
110 |
100 |
92 |
14 |
82 |
76 |
105 |
100 |
94 |
96 |
88 |
82 |
86 |
78 |
72 |
8 |
60 |
56 |
79 |
74 |
70 |
71 |
65 |
61 |
64 |
58 |
53 |
許容電流早見表
3心(共通シース形)
600V及び、3300V〜6600V CVケーブル
布設条件 |
電線管内
布設 |
管 路 布 設 (深さ1,400mm) |
|
1条
(1回線) |
1条
(1回線) |
2条
(2回線) |
31条
(3回線) |
|
直射日光無 |
損 失 率
( LF ) |
損 失 率
( LF ) |
損 失 率
( LF ) |
|
電線管
サイズ |
許容
電流 |
|
無 |
有 |
0.6 |
0.8 |
1.0 |
0.6 |
0.8 |
1.0 |
0.6 |
0.8 |
1.0 |
600V 325 |
104 |
450 |
515 |
490 |
465 |
470 |
440 |
415 |
420 |
385 |
355 |
250 |
92 |
380 |
445 |
420 |
405 |
405 |
380 |
360 |
365 |
335 |
310 |
200 |
92 |
335 |
390 |
375 |
355 |
360 |
340 |
320 |
320 |
295 |
275 |
150 |
75 |
265 |
325 |
310 |
295 |
300 |
280 |
265 |
270 |
250 |
235 |
100 |
75 |
210 |
255 |
245 |
235 |
235 |
225 |
210 |
215 |
200 |
185 |
60 |
63 |
150 |
190 |
180 |
175 |
175 |
165 |
160 |
160 |
150 |
140 |
38 |
51 |
110 |
145 |
140 |
135 |
135 |
125 |
120 |
125 |
115 |
110 |
22 |
39 |
77 |
100 |
100 |
98 |
99 |
94 |
90 |
91 |
86 |
81 |
14 |
31 |
59 |
79 |
77 |
75 |
75 |
72 |
69 |
70 |
66 |
69 |
8 |
31 |
43 |
57 |
56 |
54 |
55 |
53 |
51 |
51 |
48 |
46 |
5.5 |
31 |
35 |
46 |
45 |
44 |
44 |
43 |
41 |
41 |
39 |
38 |
3.5 |
25 |
26 |
35 |
34 |
34 |
34 |
33 |
32 |
32 |
30 |
29 |
2 |
25 |
19 |
25 |
25 |
24 |
24 |
23 |
23 |
23 |
22 |
21 |
3K-6K325 |
5B |
465 |
520 |
495 |
475 |
475 |
445 |
420 |
425 |
390 |
360 |
250 |
5B |
400 |
445 |
425 |
405 |
410 |
380 |
360 |
365 |
335 |
310 |
200 |
104 |
340 |
395 |
375 |
360 |
360 |
340 |
320 |
325 |
300 |
280 |
150 |
92 |
285 |
330 |
315 |
305 |
305 |
290 |
275 |
275 |
255 |
240 |
100 |
82 |
220 |
255 |
245 |
235 |
240 |
225 |
215 |
215 |
200 |
185 |
60 |
82 |
160 |
190 |
180 |
175 |
175 |
165 |
160 |
160 |
150 |
140 |
38 |
75 |
120 |
145 |
140 |
135 |
135 |
130 |
125 |
125 |
115 |
110 |
22 |
63 |
89 |
105 |
100 |
100 |
100 |
97 |
92 |
93 |
88 |
83 |
14 |
63 |
69 |
83 |
80 |
78 |
79 |
75 |
72 |
73 |
68 |
65 |
8 |
63 |
52 |
61 |
59 |
58 |
58 |
55 |
53 |
54 |
51 |
48 |
許容電流早見表
トリプレックス形
600V及び、3300V〜6600V CVーTケーブル
布設条件 |
気中布設 |
直 埋 布 設 (深さ1,400mm) |
|
1条
(1回線) |
1条
(1回線) |
2条
(2回線) |
31条
(3回線) |
|
直射日光
(日射) |
損失率
( LF ) |
損失率
( LF ) |
損失率
( LF ) |
|
無 |
有 |
0.6 |
0.8 |
1.0 |
0.6 |
0.8 |
1.0 |
0.6 |
0.8 |
1.0 |
600V 400 |
730 |
625 |
610 |
720 |
655 |
680 |
600 |
540 |
585 |
515 |
460 |
325 |
635 |
555 |
735 |
650 |
590 |
615 |
540 |
485 |
525 |
460 |
415 |
250 |
535 |
480 |
640 |
565 |
515 |
535 |
470 |
425 |
460 |
400 |
360 |
200 |
465 |
420 |
570 |
505 |
460 |
475 |
420 |
380 |
410 |
360 |
320 |
150 |
380 |
355 |
490 |
435 |
395 |
410 |
360 |
325 |
350 |
305 |
275 |
100 |
290 |
280 |
390 |
345 |
315 |
325 |
285 |
260 |
280 |
245 |
220 |
60 |
210 |
205 |
295 |
260 |
235 |
245 |
215 |
195 |
210 |
185 |
165 |
38 |
155 |
155 |
225 |
205 |
185 |
190 |
165 |
150 |
160 |
140 |
130 |
22 |
110 |
110 |
165 |
150 |
135 |
140 |
125 |
110 |
120 |
105 |
97 |
3K-6K400 |
745 |
610 |
795 |
710 |
650 |
680 |
600 |
545 |
590 |
520 |
470 |
325 |
655 |
545 |
715 |
640 |
585 |
610 |
540 |
490 |
530 |
465 |
420 |
250 |
555 |
470 |
620 |
555 |
510 |
530 |
470 |
425 |
460 |
405 |
365 |
200 |
480 |
415 |
550 |
495 |
455 |
470 |
420 |
380 |
410 |
360 |
325 |
150 |
400 |
350 |
470 |
425 |
390 |
405 |
360 |
325 |
350 |
310 |
280 |
100 |
305 |
275 |
375 |
340 |
310 |
320 |
285 |
260 |
280 |
245 |
225 |
60 |
220 |
205 |
280 |
255 |
235 |
240 |
215 |
195 |
210 |
185 |
170 |
38 |
165 |
155 |
215 |
195 |
180 |
185 |
165 |
150 |
165 |
145 |
130 |
22 |
120 |
110 |
160 |
140 |
135 |
135 |
125 |
110 |
120 |
105 |
98 |
許容電流早見表
トリプレックス形
600V及び、3300V〜6600V CVーTケーブル
布設条件 |
電線管内
布設 |
管 路 布 設 (深さ1,400mm) |
|
1条
(1回線) |
1条
(1回線) |
2条
(2回線) |
31条
(3回線) |
|
直射日光無 |
損 失 率
( LF ) |
損 失 率
( LF ) |
損 失 率
( LF ) |
|
電線管
サイズ |
許容
電流 |
|
無 |
有 |
0.6 |
0.8 |
1.0 |
0.6 |
0.8 |
1.0 |
0.6 |
0.8 |
1.0 |
600V 400 |
92 |
535 |
640 |
600 |
570 |
575 |
530 |
495 |
530 |
485 |
450 |
325 |
92 |
475 |
565 |
530 |
500 |
505 |
470 |
435 |
440 |
400 |
370 |
250 |
82 |
395 |
485 |
455 |
430 |
435 |
405 |
380 |
385 |
350 |
325 |
200 |
75 |
340 |
425 |
400 |
385 |
385 |
360 |
335 |
340 |
310 |
290 |
150 |
63 |
275 |
350 |
335 |
315 |
320 |
300 |
280 |
285 |
260 |
240 |
100 |
63 |
215 |
275 |
260 |
250 |
250 |
235 |
220 |
225 |
205 |
195 |
60 |
51 |
150 |
200 |
195 |
185 |
185 |
175 |
165 |
170 |
155 |
145 |
38 |
39 |
110 |
155 |
150 |
140 |
145 |
135 |
130 |
130 |
120 |
115 |
22 |
39 |
82 |
110 |
105 |
105 |
105 |
100 |
96 |
97 |
91 |
85 |
3K-6K400 |
6B |
585 |
650 |
610 |
575 |
585 |
540 |
500 |
505 |
460 |
425 |
325 |
104 |
500 |
580 |
545 |
515 |
520 |
450 |
450 |
455 |
415 |
380 |
250 |
104 |
430 |
500 |
470 |
445 |
450 |
420 |
390 |
395 |
360 |
335 |
200 |
92 |
370 |
435 |
410 |
390 |
385 |
365 |
345 |
345 |
315 |
295 |
150 |
82 |
305 |
365 |
345 |
330 |
335 |
310 |
290 |
295 |
270 |
250 |
100 |
75 |
235 |
285 |
275 |
260 |
265 |
245 |
230 |
235 |
215 |
200 |
60 |
75 |
175 |
210 |
200 |
190 |
195 |
180 |
170 |
175 |
160 |
150 |
38 |
63 |
130 |
160 |
150 |
145 |
145 |
140 |
130 |
175 |
125 |
115 |
22 |
63 |
95 |
115 |
110 |
105 |
110 |
100 |
99 |
100 |
93 |
87 |
●技術資料 目次 ●ページの先頭 ●次ページ
|